Two-column water softener BWT EUROSOFT TWIN WS 1'' 0844
Availability: In stock
Two-column water softener BWT EUROSOFT ETWIN WS 1'' 0844
Description
Two-column softener BWT EUROSOFT TWIN WS 1'' 0844 with volume control, operating in pendulum mode - provides continuous supply of softened water or partially softened water in domestic and drinking water supply systems and in water treatment systems for feeding heating systems.
The scope of delivery includes: one multi-way control valve (optionally with a residual hardness regulator), a flow meter (built into the softened water pipeline), two ion exchange columns (the bodies of which are made of food-grade plastic reinforced with fiberglass), a certified ion exchange resin, a brine tank in complete, a hose for discharging wash water into the drain, a tester for the total hardness AQUATEST.
Advantages:
- Electronic volume control;
- Continuous supply of softened water - pendulum mode of operation of the installation;
- Corrosion-resistant construction materials provide exceptional durability of the unit;
- One multifunctional control valve ensures the automated system operation of the plant;
- Convenience in programming - setting the frequency of regeneration depending on the volume of water consumed, peak flow and the required time of day;
- The control valve can be equipped with a residual hardness regulator (option);
Characteristics
Nominal connection diameter, DN | 25 (1˝) |
Nominal consumption during softening up to 0.1 d°, m 3 /hour | 0.8 |
Maximum consumption, m 3 / hour | 1.1 |
Pressure loss at nominal flow, bar | 0.5 |
Pressure loss at maximum flow, bar | 1.0 |
Maximum amount of softened water between regenerations at softening up to 15 d°, m 3 /hour | 2.5 |
Ion-exchange capacity of one column, m 3 x d° | 40 |
Average salt consumption per regeneration, kg | four |
Working pressure, bar | 3-7 |
Water/environment temperature, o С | 30/40 |
Overall height, mm | 1316 |
Total depth, mm | 490 |
Overall width, mm | 1023 |
Power supply, V/Hz | 24/50 |