Heating automation kit with Honeywell Smile SDC3-10N controller
Availability: In stock
- Weather-dependent boiler temperature control.
- Pump control for the direct circuit of the heating system.
- DHW pump control (various priority modes).
- Independent seven-day temporary programs.
Price available upon request
Heating automation kit with Honeywell Smile SDC3-10N controller
Components of the automation system | Quantity | |
SDC3-10N | Smile controller, 1 stage, 1 direct circuit, DHW | 1 PC. |
TBS-Smile | Panel Mount Terminal Block Set | 1 PC. |
KTF20-65-2M | Boiler and DHW tank temperature sensor | 2 pcs. |
AF20-B54 | Outdoor temperature sensor | 1 PC. |
1. Honeywell Smile SDC3-10N controller
Smile SDC controllers version 3.2 are designed to control heating and hot water systems with one or more boilers (SDC mode) or district heating system heat exchangers (DHC mode). All controllers are equipped with a large, backlit LCD display that provides easy-to-read system parameters. Convenient intuitive controller interface now supports Russian. The buttons for quick access to setting the main parameters, operating modes, indoor air temperature and hot water temperature in the boiler are placed on the front panel.
Principle of operation:
Heating and DHW circuits are controlled independently, 7-day time programs offer up to 2 comfort and 3 economy periods per day. For each heating circuit, you can set an individual temperature-time program, taking into account weather compensation or taking into account maintaining a constant temperature of the heat carrier in the circuit. This feature will allow the use of two circuits in one heating zone. For example, one circuit is used for underfloor heating with a constant flow temperature, and the other for radiator heating, taking into account weather compensation.
Controller Features:
- Convenient and intuitive operation with the controller is ensured by a spacious 3-line LCD display with backlight, a rotary push button and main quick access buttons placed on the front panel;
- The controller menu supports Russian;
- Different access levels to the settings (User menu, Service Engineer menu) provide protection against unauthorized changes;
- Remote change of operating modes and settings when using SDW10, SDW20 or SDW30 room modules;
- Up to 15 vacation periods (school holidays, weekends, etc.) can be programmed both in advance and after the onset;
- Special energy-saving modes: Permanent economy, Absence, Vacation, Off, help save heating costs;
- Support for the OpenTherm protocol when controlling boilers;
- Frost protection;
- Legionella protection (for DHW systems);
- Protection of valves and pumps from sticking.
2. TBS-Smile Panel Mount Terminal Block Set
TBS-Smile terminal blocks are designed for connecting el. wires to the controller in case you plan to install the controller on the control panel door or on the boiler panel. The TBS-Smile package includes four terminal blocks at once: X1, X2, X3, X4.
3. Cable type temperature sensor KTF20-65-2M
The cable type temperature sensor KTF20 is used in heating systems to measure the temperature of the coolant in the pipe.
Characteristics:
- Protection class: IP65
- Temperature range: -30...105 °C
- Cable length: 2m
- Diameter x Length: 6.0 x 55 mm
4. Outdoor temperature sensor AF20-B54
Characteristics:
- Protection class: IP54
- Temperature range: -40...+70 °C
- Number of wires to be connected: 2
- Size (HxWxD): 81 x 56 x 56 mm